3000 Watt Rackmount DC-AC Inverter
This power inverter provides seamless back-up power for AC powered communications equipment from the site’s 48V DC battery system. A fast-acting transfer switch ensures voice and data transmissions remain uninterrupted in the event of a power grid failure or if the site utility power is disconnected for maintenance and upgrade purposes. Built in a 2RU case for 19″ rack installations.
Features
- Pure sine wave AC output powers telecom equipment without performance degradation
- Continuous duty rated – full output wattage maintained even during extended power outages
- 3000 Watts – easily cascaded for N+1 redundancy, providing maximum reliability required by data centers
- Low EMI and RFI interference characteristics
- High efficiency: 89% (Full linear load at 120 VAC Output)
- Four NEMA 5-15R AC receptacles provided
- Utility bypass, with fast load transfer switch, <6mS
- Numerous circuit and load protections: over- temp, overload, reverse polarity, high/low battery voltage, AC input breaker
- Load & temperature controlled cooling fan
- Form C alarm contacts for monitoring Abnormal conditions
- All diagnostic Operation Controlled by a microprocessor
- User-friendly Status and Diagnostic LED displays
- Remote Power Management optional via remote control relay RS-232 port
- Inverter model/UPS mode switch
- Standard 19″ 2U Rackmount
Specifications: Rackmount Inverter – 3000 Watts
Model | DC Input | AC Output | Weight (Lbs.) | |
---|---|---|---|---|
Voltage | Amps | Volts/Watts | ||
48-3000RM | 42 – 62 | 75 | 120 VAC/3000 | 31.5 |
AC Characteristics
Voltage: 100-120 VAC (select using front panel potentiomet); Factory set at 120 VAC
Frequency: 60 Hz. Standard, 50 Hz. User selectable
Wave Form: Pure Sine
Total Harmonic Distortion: THD <3%
Transfer Time: 4-6 ms
From AC bypass mode: ≤ 20mS
From Inverter mode: ≤ 8mS
Input:
No Load Current: .39A
Over Voltage Protection: 62 VDC
Under Voltage Protection: 42 VDC
Voltage Range: 42-62 VDC
Efficiency: 89%( Full Load)
Output:
Voltage: 120 VAC
Max Output Power (3min): 3200W
Surge Power: 3500W (3 sec.)
Peak: 6,000W (<1 sec.)
Displays:
LED: Online, Bypass, Inverter Mode, UPS Mode, Back-Up
LCD: 2 line LCD w/ Keypad for navigation
Selectable Functions: Output Voltage, Amperage, Watts, VDC In, Temperature, Frequency settings
Operating Temperature: -20° to 50° C Full Load
Storage Temperature: -30° to 70° C
Cooling: Forced air, front-to-back On @ 300W load or elevated,
Humidity: 0-90% relative humidity
Visual & Audio Alarms:
- Form C (Dry Contact) terminals: Summary alarm
- Overload / Short Circuit Alarm
- Input UV / OV
- Over Temperature
- Inverter Fail
Communication Interface
RS-232 port with user selectable, Remote control of inverter (on/off)
Mechanical
Dimensions: 17.52″W x 3.46″H x 16.7″D
Mounting: 19″ two post relay rack (flush or 6″ set-back) and 19″ four post cabinet mount
EMC & Safety Standards
EN60950-1
EN 55022:2006, Class A
En61000-3-2: 2006
En61000-3-3: 1995+A1; 2001+A2:2005