The Power Function Manager (PFM-500) is a system integrating component which converts ordinary power supplies (or Power Modules) into a fully integrated and multifunctional power system. The unit provides for control, monitoring, paralleling and protection of 12, 24 or 48 VDC, positive negative or floating ground power sources.
A 500 amp, heavy duty parallel tie point bus accommodates input from multiple/redundant rectifiers. A digital meter displays system bus voltage, battery voltage, total rectifier amperage, connect/disconnect voltage set points, and system ambient temperature. Features also include status lights, load distribution circuits, low voltage battery disconnect with alarm contacts. All these functions are combined in a compact, rackmount housing which serves as a master DC power management and distribution center. A rackmount ground/return bus is provided.
The PFM may be used for integration, control, monitoring and protection of numerous different types of power sources, such as AC-DC rectifiers, regulated power supplies, DC-DC converters and battery banks.
Specifications: Power Function Manager - PFM-500
Model | Nominal Input/Output VDC | Circuit Breaker Capacity |
---|---|---|
PFM-500 | 12, 24, or 48 pos. or neg. ground | 5 (PBA Series) |
Features
- Provides parallel tie point for DC power modules; simplifies wiring
- 12, 24 or 48 VDC input/output, positive or negative ground; can be used with virtually any DC system
- Use with positive, negative or floating ground; no need to stock multiple units
to meet different site requirements - Digital meter displays: system bus voltage, battery voltage, total rectifier amperage,
connect/disconnect voltage set points, and system ambient temperature - Up to five isolated distribution circuit breaker capacity with "BREAKER TRIP" alarm
contacts; easy front panel plug-in installation. Breakers sold separately - Alarm LED (summary) indicates impending LVD disconnection, Power Module output
fail or load circuit breaker trip - Summary alarm contacts (form C) allow remote monitoring of system status in the
event of extended AC power loss - Manual battery disconnect switch allows service/replacement of batteries without system shutdown
- High current output bus for wiring main system load or for feeding an external distribution panel
- Ground bus provided
- Low voltage battery disconnect protects batteries in the event of extended AC power loss
Overall Performance
Input/Output: 12, 24 or 48 VDC nominal, positive or negative ground
Voltage Range: 8 - 65 VDC
Grounding: Positive or Negative (Polarity insensitivity)
Maximum Total Current Capacity: 500 amps (max. 6 power supply/modules maximum)
Temperature Rating: 0° C to +60° C
Protection
- Five branch circuit breakers (optional)
- Low voltage battery disconnect (See LVBD Specifications below)
Mechanical/General
- Heavy duty plated copper bus bar
- Powder coated aluminum chassis
- 19" or 23", 2 RU, flush or 6” forward rackmount
Case Size
Inches | Centimeters | Weight | ||||||
---|---|---|---|---|---|---|---|---|
H | W* | D | H | W* | D | lbs | Kg | |
3.5 | 17 | 20.5 | 13.5 | 43.2 | 52.1 | 20 | 9.1 | |
*19” and 23” mounting brackets provided |
Indicators/Alarms
- "ALARM" (summary) L.E.D. indicator (Red)
- Digital volt/amp meter (selectable)
- Form C summary alarm contacts; provide for monitoring of up to six inputs from equipment with either Form C or Normally Open contacts. Typical indications include Power Module failure, LVBD activation, breaker mid-trip condition
- A separate set of Form C contacts are provided for pre-LVD activation
Rear Panel
Low Voltage Battery Disconnect Specifications
Factory set actuation voltages:
12 VDC | 24 VDC | 48 VDC | |
---|---|---|---|
Connect | 10.4V | 21.0V | 42.0V |
Disconnect | 12.0V | 24.5V | 49.0V |
Factory default LVD pre-disconnect warning alarm threshold (adjustable):
12 VDC | 24 VDC | 48 VDC | |
---|---|---|---|
LVD Pre-Disconnect | 11.2V | 26.2V | 45.5V |
Options:
- Plug-in mid-trip circuit breakers with auxiliary contacts that activate “CHECK SYSTEM” indicator and summary alarm contacts. Available Amperages:
- 5, 10, 15, 20, 30, 40, 50, 75, 100 (specify model PBA-5, PBA-10, etc.)
- Quick connect DC wiring harness for use with Newmar 1 KW Power Modules; QCK-3, CCK-4
- Rear Rack Covers: RRC-7-19 or RRC-7-23 (click here)
- Power Modules
- Additional Distribution: Model DST-10 (UL) or DST-20A(UL)